VFD Motor Cable Derating & Shielded Cable Calculator

Conductor derating and shielded cable specs for variable-frequency drive installs

Ad placeholder (leaderboard)

Conductors feeding a variable-frequency drive carry more than ordinary motor current — they also carry high-frequency switching energy that ordinary cable in conduit handles badly. This calculator sizes the branch-circuit conductor to NEC 430.22(A), applies the ambient and bundling derates, and then recommends a shielded VFD cable and a high-frequency drain ground so the installation is both code-compliant and electrically clean.

How it works

The required conductor ampacity is built up in three steps and then matched to a real conductor:

required      = motor FLA × 1.25            (NEC 430.22(A))
derated req.  = required / (ambient factor × bundling factor)
conductor     = smallest 75°C Cu size whose table ampacity ≥ derated req.

The ambient correction factors come from NEC 310.15(B)(1) for 75°C insulation, and the bundling adjustment factors from NEC 310.15(C)(1) for the count of current-carrying conductors. Dividing the 125% requirement by these factors is the correct way to make sure the installed conductor still clears the required load after it is derated for its real-world conditions.

Shielded cable and grounding notes

For the cable type, NEMA 250 and IEEE 1100 recommended practice is a listed VFD or Type WTTC cable with a continuous shield of at least 85% coverage and a symmetrical drain. The drive ground should be sized to carry high-frequency leakage current — match it to the phase-conductor gauge or use three symmetrical grounds — rather than the smaller equipment-grounding conductor from NEC Table 250.122. A low-impedance HF return path is what prevents motor bearing damage and nuisance EMI on nearby control wiring.

Example and tips

A 21 A motor at 30 °C with three current-carrying conductors needs 21 × 1.25 = 26.25 A, which 10 AWG copper (35 A) covers comfortably. Raise the ambient to 40 °C and the same load needs 26.25 / 0.88 = 29.8 A, still met by 10 AWG. Always keep the VFD cable run as short and direct as practical, bond the shield at both ends, and verify the result against the adopted NEC edition and the drive manufacturer’s installation manual.

Ad placeholder (rectangle)