NEC Kitchen Circuit Requirements Calculator

List the dedicated kitchen circuits required per NEC 210.52, 210.8, and 210.12

Ad placeholder (leaderboard)

A code-compliant residential kitchen needs more dedicated circuits than almost any other room. This tool takes the list of appliances you are wiring and returns the minimum required circuits per NEC 210.52, with the conductor size and GFCI/AFCI protection for each, so nothing gets shared that the code says must be dedicated.

How it works

The list always starts with the two mandatory small-appliance circuits, then adds an individual circuit per built-in appliance:

always:  2 × 20 A small-appliance circuits   (NEC 210.52(B), 12 AWG Cu)
+ each selected appliance → its own dedicated circuit
countertop receptacles  → GFCI (210.8(A))
kitchen branch circuits → AFCI (210.12)

The two small-appliance circuits serve the countertop receptacles and may extend to the dining room, but they cannot carry lighting or feed the built-in appliances. Each fixed appliance — dishwasher, disposal, microwave, and an electric range — gets its own circuit sized to its nameplate.

Example and notes

A typical full kitchen with a refrigerator, dishwasher, disposal, built-in microwave, and electric range needs seven circuits: the two small-appliance circuits plus one each for the five appliances. Swap the electric range for gas and the range simply rides the small-appliance circuit for its igniter, leaving you with the same count but a lighter service draw. Always verify the adopted NEC edition and any local amendments, since AFCI and GFCI scope has expanded across recent code cycles, and confirm each appliance’s nameplate before final breaker and conductor selection.

Ad placeholder (rectangle)