Box Fill Calculator (NEC 314.16)

Sum conductor, device, clamp, and fitting equivalents to verify junction/outlet box fill

Ad placeholder (leaderboard)

Overfilling an electrical box damages insulation, makes terminations unreliable, and fails inspection. NEC 314.16(B) assigns a cubic-inch allowance to every item in the box; this tool sums them under the correct counting rules and checks the total against the box’s listed volume.

How it works

Each category gets a volume allowance, with clamps, studs, devices, and the grounding allowance all based on the largest conductor present:

conductors = count × allowance(conductor gauge)
devices    = device count × 2 × allowance(largest conductor)
clamps     = (any clamps ? 1 : 0) × allowance(largest conductor)
studs      = fitting count × allowance(largest conductor)
grounds    = (any EGC ? 1 : 0) × allowance(largest EGC)
required   = sum of the above

If the required fill is at or below the box’s listed volume the box is compliant; otherwise it is overfilled.

Example and notes

A box with six 12 AWG conductors (6 × 2.25 = 13.5), one device (2 × 2.25 = 4.5), internal clamps (2.25), and a 12 AWG grounding allowance (2.25) needs 22.5 cubic inches, so an 18-cubic-inch box would be overfilled and a deeper box is required. Note that the listed volume of a box is stamped on it or published by the manufacturer; never estimate it from outside dimensions, since internal volume is reduced by the box walls and any plaster ring adds capacity.

Ad placeholder (rectangle)