On a 120/240 V single-phase panel the shared neutral carries only the difference between the two hot legs, so spreading the 120 V loads evenly minimizes neutral current and balances the panel. This calculator takes your circuit list, reports per-leg totals and the neutral imbalance, and suggests a reassignment that brings the panel within a 10% balance target.
How it works
Each circuit’s VA is summed by leg, converted to amps, and compared:
leg A amps = sum of leg-A VA / 120
leg B amps = sum of leg-B VA / 120
neutral amps = | leg A amps − leg B amps |
imbalance % = | leg A VA − leg B VA | / max(leg A VA, leg B VA) × 100
A 240 V two-pole circuit loads both legs equally and cancels in the neutral, so it is excluded from the imbalance figure. The rebalancer sorts the 120 V circuits largest-first and drops each onto the lighter leg, which closely approaches the best possible split.
Example and tips
Suppose leg A carries 5000 VA and leg B carries 3000 VA. Leg A draws about 41.7 A,
leg B about 25 A, so the neutral carries roughly 16.7 A and the panel is
(5000 − 3000) / 5000 = 40% out of balance. Moving a 1000 VA circuit from A to B
brings the legs to 4000 and 4000, dropping the neutral current to near zero. Tips:
balance by running load rather than breaker count, since a single large circuit
can outweigh several small ones; keep 240 V loads in the list for capacity even
though they do not affect balance; and rebalance again after adding any large new
circuit such as an EV charger or electric range.