Feeder taps let a large feeder branch off into a smaller conductor without its own overcurrent device — but only inside the narrow exceptions NEC 240.21(B) allows. This calculator checks a proposed tap against the 10-ft, 25-ft, and outside-tap rules at once so you know whether the conductor is legal before you pull it.
How it works
Each rule sets a minimum tap ampacity tied to the feeder’s overcurrent device rating, with a length ceiling:
10-ft rule: length ≤ 10 ft tap ampacity ≥ 10% of feeder OCPD
25-ft rule: length ≤ 25 ft tap ampacity ≥ 1/3 of feeder OCPD
outside rule: any length single OCPD at building entry, damage-protected
The tool computes both thresholds from the feeder rating and reports which rules the tap satisfies. Passing any one rule, with its termination and enclosure conditions met, makes the tap compliant.
Example and notes
A 175 A tap off a 400 A feeder, run 20 ft, fails the 10-ft rule on length and fails the 25-ft rule because one-third of 400 A is 133 A — wait, 175 A exceeds 133 A, so it actually passes the 25-ft rule as long as it terminates in a single device rated 175 A or less. Shorten that same tap to 8 ft and it must instead carry at least 40 A (10 percent of 400 A), which it easily does. Always confirm the termination and physical-protection conditions, and remember tap ampacity is the derated value, not the bare table figure.