Every piece of electrical equipment must be rated to withstand the fault current available where it is installed, per NEC 110.10. This calculator uses the industry-standard Bussmann point-to-point method to find that available short-circuit current at any node — a switchboard, panelboard, or motor control center — so you can compare it against equipment SCCR and breaker AIC ratings.
How it works
First, the fault current at the transformer secondary, assuming an infinite primary bus:
I_fla = kVA × 1000 / (V × √3) (three-phase)
I_sca = I_fla / (%Z / 100)
Then a conductor run reduces the current. The point-to-point factor f and
multiplier M propagate the fault through the conductor:
f = (√3 × L × I_sca) / (C × n × V)
M = 1 / (1 + f)
I_at_point = I_sca × M
Here L is the one-way length in feet, C is the Bussmann conductor constant
for the size and material, n is the number of parallel conductors per phase,
and V is the line-to-line voltage.
Reading the result
The tool reports the transformer full-load current, the secondary fault current, the conductor multiplier, and the final available fault current at the point. Your equipment SCCR and each breaker’s AIC must equal or exceed that final figure.
Example and notes
A 500 kVA, 5.75%Z, 480 V three-phase transformer delivers about 10,460 A full-load and roughly 18,200 A of fault current at its secondary terminals. Running 100 ft of 4/0 copper to a downstream panel drops the available fault current meaningfully through the multiplier. The infinite-bus assumption is deliberately conservative; supplying a known primary fault current would lower the result, so the value shown is the safe worst case for selecting rated equipment.