NEC GFCI/AFCI Requirement Checker

Look up 2023 NEC GFCI and AFCI protection requirements by room type and circuit voltage

Ad placeholder (leaderboard)

GFCI and AFCI protection requirements have expanded with nearly every NEC cycle, and they apply to different locations for different reasons. This tool maps a room or location and circuit voltage to the applicable 2023 NEC section so you can plan rough-in and verify panels before inspection.

How it works

The checker encodes two NEC rules. NEC 210.8(A) lists the dwelling locations where 125 V to 250 V receptacles up to 50 A require ground-fault protection: kitchens, bathrooms, garages, outdoors, basements, laundry areas, and within 6 ft of any sink. NEC 210.12(A) requires combination AFCI protection for all 120 V, 15 and 20 ampere branch circuits supplying outlets in dwelling living areas — bedrooms, living rooms, hallways, kitchens, laundry, and more.

Because AFCI only applies to 120 V 15/20 A circuits, selecting 240 V suppresses the AFCI requirement while leaving any applicable GFCI requirement in place.

Reading the result

Each location returns the governing section number for GFCI and AFCI, a required/not-required verdict, and a note covering the key exception. Where both are required — kitchens, basements, laundry — a dual-function device satisfies both in one breaker or receptacle.

Example and notes

A kitchen countertop circuit at 120 V needs GFCI under 210.8(A)(6) and AFCI under 210.12(A), so a dual-function breaker is the clean solution. A 240 V range receptacle in the same kitchen does not need AFCI but still needs GFCI if it is a 125/250 V receptacle covered by 210.8. Always confirm the code cycle adopted by your AHJ, as local amendments can add or remove specific requirements.

Ad placeholder (rectangle)