NEC Article 430 Motor Circuit Summary Calculator

Get FLC, conductor, max OCPD, overload, and disconnect for a motor in one step.

Ad placeholder (leaderboard)

Designing a motor branch circuit means pulling five related numbers in the right order: the full-load current, the conductor, the short-circuit and ground-fault device, the overload, and the disconnect. NEC Article 430 ties them together but spreads them across several tables and sections. This calculator reads the table values and applies each rule so you get the complete circuit summary in one step.

How it works

Full-load current comes directly from NEC Table 430.248 for single-phase motors or Table 430.250 for three-phase, indexed by horsepower and voltage. Every downstream value is derived from that FLC:

Conductor (430.22):      ampacity >= 1.25 x FLC
Max OCPD (Table 430.52): multiplier x FLC, rounded up to a standard size
   inverse-time breaker  250%   dual-element fuse  175%
   non-time-delay fuse   300%   instantaneous trip 800%
Overload (430.32):       115% or 125% of nameplate FLA
Disconnect (430.110):    >= 1.15 x FLC

The conductor is chosen from the 75 degree Celsius copper column of Table 310.16, and the OCPD is rounded up to the next standard size from 240.6(A) as permitted by 430.52(C)(1) Exception 1.

Example and notes

A 10 HP, three-phase, 460 V motor has a table FLC of 14 A. The conductor must carry 17.5 A, which a 12 AWG 75°C copper conductor satisfies. With an inverse-time breaker the maximum OCPD is 250 percent of 14, or 35 A, which is already a standard size. The overload sizes to roughly 16 to 17.5 A from nameplate, and the disconnect must be rated at least 16.1 A.

Remember the table FLC drives conductor, OCPD, and disconnect, while only the overload uses the nameplate FLA. When several motors share a feeder, size the feeder under 430.24 and apply ambient and conduit-fill corrections to the conductor ampacity shown here.

Ad placeholder (rectangle)