Equipment Grounding Conductor Sizing (NEC 250.122)

Select minimum EGC wire size from the NEC 250.122 table by OCPD rating

Ad placeholder (leaderboard)

The equipment grounding conductor is the safety path that carries fault current back to clear a breaker, and it is sized from the overcurrent device, not the load. This tool reads the minimum size straight from NEC Table 250.122 for copper or aluminum.

How it works

The lookup keys on the overcurrent protective device (OCPD) rating and returns the minimum conductor for the chosen material:

find the first table row where OCPD ≤ row maximum
EGC = copper or aluminum size in that row
if parallel sets > 1 → run that full EGC in EVERY raceway (250.122(F))

For example a 60 A circuit needs 10 AWG copper, a 200 A circuit needs 6 AWG copper, and a 400 A circuit needs 3 AWG copper.

Example and notes

A feeder protected at 200 A takes a minimum 6 AWG copper or 4 AWG aluminum grounding conductor. If that feeder is run as two parallel sets in separate conduits, each conduit must contain its own full 6 AWG copper EGC, not a half-size conductor. Remember the proportional-upsize rule in 250.122(B): increasing the phase conductors for voltage drop forces a matching increase in the grounding conductor by the same area ratio, so recompute it whenever you upsize the circuit.

Ad placeholder (rectangle)