Makeup Air Unit (MAU) CFM Calculator

Size makeup air CFM to replace exhaust and hold building pressurization

Ad placeholder (leaderboard)

A makeup air unit must replace what the building exhausts while holding the intended pressure relationship. This tool totals exhaust, applies your pressurization target and infiltration credit, and sizes both the supply CFM and the winter heating capacity of the MAU.

How it works

totalExhaust   = sum of all exhaust CFM sources
requiredMakeup = totalExhaust × (target % / 100) − infiltration credit
heatingBTU/h   = 1.08 × requiredMakeup × (supply temp − winter design temp)

Targeting slightly under 100% replacement keeps the space mildly negative — standard practice for commercial kitchens so odors do not migrate. The 1.08 constant is the sea-level sensible-heat factor for air (0.075 lb/ft³ × 60 min/hr × 0.24 BTU/lb·°F).

Example and tips

Two kitchen hoods exhausting 1,500 CFM each plus 400 CFM of restroom exhaust total 3,400 CFM. At 90% replacement with a 200 CFM infiltration credit, the MAU must supply about 2,860 CFM. Heating that air from a 5°F winter design temperature to a 65°F supply setpoint needs roughly 1.08 × 2,860 × 60 ≈ 185,000 BTU/h. In hot humid climates, size cooling and dehumidification of the makeup air separately — sensible heating alone understates the load there.

Ad placeholder (rectangle)