HVAC CFM Airflow Calculator

Calculate required supply-air CFM from a room's heat load and supply-air temperature difference

Ad placeholder (leaderboard)

The HVAC CFM airflow calculator turns a room’s heat load into the supply airflow you actually need to deliver. It uses the standard sensible-heat equation that every mechanical designer relies on to size diffusers, VAV boxes, and air-handler branches.

How it works

Required airflow comes from rearranging the two classic air-side heat equations:

sensible:  Q_s = CFM x 1.08 x dT
latent:    Q_l = CFM x 0.68 x d-grains

so:
CFM_sensible = Q_s / (1.08 x dT)
CFM_latent   = Q_l / (0.68 x d-grains)

The constant 1.08 bundles standard air density, the specific heat of air, and the 60-minutes-per-hour conversion. The latent constant 0.68 does the same but for moisture removal, using the latent heat of vaporization and 7000 grains per pound. You size the duct to whichever airflow is larger.

Example and tips

A room with a 12,000 BTU/h sensible load and a 20 F supply temperature difference needs 12000 / (1.08 x 20) = 556 CFM. If that same room also carries a 3,000 BTU/h latent load with a 25 gr/lb difference, the latent airflow is 3000 / (0.68 x 25) = 176 CFM, so the sensible requirement governs and you design for about 556 CFM. Keep your delta-T realistic: pushing it above 22 F to shrink ducts often causes cold drafting at the diffusers.

Ad placeholder (rectangle)