A gas meter and its first-stage regulator must be able to deliver the peak gas demand of every appliance behind it. This calculator sums each appliance’s BTU/h input, applies a realistic diversity factor, converts the result to standard cubic feet per hour for natural gas or propane, and checks it against the rated meter capacity so you can confirm the service is adequate before you connect a new appliance.
How it works
Three steps turn a list of appliances into a meter capacity check:
connected load = Σ appliance BTU/h
design demand = connected load × diversity factor
SCFH = design demand / heating value per cubic foot
The heating value is about 1030 BTU per cubic foot for natural gas and 2516 for propane vapor, so the same BTU/h load draws far fewer cubic feet of propane. The design demand in SCFH is then compared to the meter or regulator’s rated SCFH; if demand exceeds capacity the service is undersized.
Example and tips
A furnace at 80,000, a water heater at 40,000, and a range at 65,000 BTU/h give a connected load of 185,000 BTU/h. With a 0.80 diversity factor the design demand is 148,000 BTU/h, which on natural gas is about 144 SCFH — comfortably inside a 250 SCFH meter. Always confirm the diversity factor your jurisdiction allows; some authorities require full simultaneous demand for commercial kitchens and other high-use occupancies, in which case set the factor to 1.00.