A panel audit catches the faults that cause nuisance trips, overheating, and failed inspections: circuits loaded past their safe limit, breakers larger than the wire they protect, and missing arc-fault or ground-fault protection. This tool screens each circuit against the three rules at once.
How it works
Each circuit is checked against three independent rules:
overload : connected load > 0.80 × breaker amps → FAIL
conductor : wire ampacity (NEC 310.16 75C) < breaker → FAIL
AFCI : circuit type requires AFCI and none present → FAIL
GFCI : circuit type requires GFCI and none present → FAIL
Conductor ampacity uses the NEC 310.16 75°C copper column: 14 AWG = 20A (15A breaker max), 12 AWG = 25A (20A max), 10 AWG = 35A (30A max), 8 AWG = 50A, 6 AWG = 65A, 4 AWG = 85A, 3 AWG = 100A, 2 AWG = 115A, 1 AWG = 130A. The breaker must not exceed the conductor’s protected rating.
Example and tips
A 20A breaker feeding a kitchen circuit with a 14A connected load and 12 AWG copper passes the conductor check but fails the 80% rule (14A > 16A limit is false, so it passes) — adjust the load to 17A and it flags as overloaded. A kitchen circuit with no AFCI marked is flagged regardless of load. Always derate conductor ampacity for high ambient temperature and conduit fill before relying on the table values; this tool uses the base 75°C figures.