Grounding & Bonding Checklist Generator (NEC 250)

Generate a site-specific NEC Article 250 grounding and bonding checklist

Ad placeholder (leaderboard)

NEC Article 250 governs how a service is grounded and bonded, and inspectors check it closely. This generator turns your service details into a printable checklist of the specific connections required, with the grounding electrode conductor and bonding jumpers sized straight from the NEC tables.

How it works

Two NEC tables drive the conductor sizing. The grounding electrode conductor comes from Table 250.66 indexed by the largest ungrounded service conductor, and equipment bonding jumpers come from the same table for the supply side. The tool applies these rules:

GEC size       ← Table 250.66 (by largest service conductor)
to ground rods ← never larger than 6 AWG copper (250.66(A))
main bonding   ← main service only; subpanels keep neutral and ground separate
electrodes     ← all present electrodes must be bonded together (250.50)

Based on the panel type it includes either a main bonding jumper (service) or separated neutral and ground buses plus a feeder equipment grounding conductor (subpanel), then lists every electrode and bonding connection you have to make.

Example and notes

A 200 A service with 2/0 copper conductors gets a 4 AWG copper grounding electrode conductor (Table 250.66), but the run to a pair of ground rods only needs 6 AWG. If a concrete-encased electrode exists it must be used; if metal water piping is present it must be bonded. At a subpanel, remove the main bonding jumper, isolate the neutral bus, and run a separate equipment grounding conductor with the feeder. Always confirm against the NEC edition adopted by your local authority having jurisdiction.

Ad placeholder (rectangle)