Subpanel Sizing Calculator

Determine subpanel ampacity, feeder wire, and breaker size from your circuit load list.

Ad placeholder (leaderboard)

A subpanel feeder is sized from the loads it actually serves, after the NEC allows realistic demand reductions. This calculator sums your connected loads, applies the NEC 220.42 demand factor, and returns the minimum subpanel ampacity, the copper feeder conductor, the main breaker rating, and a feeder voltage-drop check for garages, workshops, ADUs, and tenant build-outs.

How it works

Loads are entered in volt-amperes (watts) so the code demand factors apply directly:

general demand  = first 3000 VA × 100% + remainder × 35%   (NEC 220.42)
total demand    = general demand + appliances + continuous × 1.25 + larger of heat/AC
feeder amps     = total demand / feeder voltage
breaker (OCPD)  = next standard breaker ≥ feeder amps
conductor       = smallest 75°C copper wire with ampacity ≥ feeder amps
voltage drop    = feeder amps × 2 × R_per_1000ft × length / 1000

The 35% demand factor on general lighting reflects that not every receptacle and light runs simultaneously, while continuous loads are kept at 125% because they run for hours at a time.

Example and tips

A workshop subpanel with 8000 VA of general lighting, 6000 VA of fixed appliances, a 3000 VA continuous load, and a 5000 VA heater works out to roughly (3000 + 5000 × 0.35) + 6000 + 3750 + 5000 = 19,500 VA, or about 81 A at 240 V, calling for a 100 A subpanel on a 3 AWG copper feeder. Tips: enter the larger of heat or cooling only, never both, since they rarely run together; keep the feeder voltage drop under 3% by upsizing on long runs; and remember the panel bus rating must be at least the feeder breaker, even if the load is smaller.

Ad placeholder (rectangle)