Lighting Circuit Load Calculator

Calculate the number of lighting fixtures per 15 A or 20 A circuit using the 80% continuous-load rule

Ad placeholder (leaderboard)

Laying out a lighting panel comes down to one question: how many fixtures can each branch circuit carry. Because lighting is a continuous load, the answer is not the full circuit rating but 80 percent of it. This calculator applies that rule and tells you fixtures per circuit and total circuits for the space.

How it works

The circuit’s volt-ampere capacity is its voltage times its breaker amps. The continuous-load rule caps usable capacity at 80 percent of that:

circuit VA        = voltage × breaker amps
usable VA         = circuit VA × 0.80
fixtures/circuit  = floor( usable VA / fixture VA )
circuits needed   = ceil( total fixtures / fixtures per circuit )

The 80 percent factor is the inverse of the NEC 210.20(A) requirement that the breaker be rated 125 percent of a continuous load. Using the floor and ceiling functions keeps fixture counts whole and never overloads a circuit.

Worked example

A 20 A 120 V circuit provides 2400 VA, of which 1920 VA is usable. With 60 W fixtures that is 32 fixtures per circuit. A space with 40 such fixtures therefore needs 2 circuits, the second lightly loaded. At 277 V the same 20 A breaker gives 4432 VA usable, more than doubling the fixtures per circuit.

Notes

Always size from the fixture’s labeled input wattage or VA, not the bare lamp wattage, since LED drivers and ballasts add real load. Where the label gives input amps, use those directly. Leave headroom for future additions rather than packing each circuit to the exact maximum.

Ad placeholder (rectangle)