This calculator turns a duct blaster reading into the two numbers that matter for commissioning and energy-code compliance: leakage per 100 ft² of conditioned area (the IECC 2021 metric) and leakage as a percentage of system airflow (the Manual D diagnostic). It then flags pass or fail.
How it works
A duct blaster pressurises the duct system to a reference 25 Pascals and reports the fan flow needed to hold that pressure — the CFM25 reading. From that:
leakage per 100 ft² = CFM25 ÷ conditioned area × 100
% of system airflow = CFM25 ÷ system airflow × 100
IECC 2021 judges compliance on the per 100 ft² figure. For a system with 80 CFM25 leakage serving 2,000 ft²:
80 ÷ 2000 × 100 = 4.0 CFM25 / 100 ft²
That exactly meets the 4.0 limit for a final, air-handler-installed test — a pass.
Code thresholds
| Test type | IECC 2021 limit |
|---|---|
| Post-construction (final) | ≤ 4.0 CFM25 / 100 ft² |
| Rough-in, air handler installed | ≤ 4.0 CFM25 / 100 ft² |
| Rough-in, no air handler | ≤ 3.0 CFM25 / 100 ft² |
Notes
The percentage-of-airflow figure is shown for ACCA Manual D commissioning reference, where 6% or less is a common “tight system” target. Always seal, then re-test: most failures come from disconnected boots, unsealed plenum seams, and leaky return chases. Local code amendments can tighten these limits, so confirm the adopted version in your jurisdiction.