VAV Box Sizing Calculator

Size VAV terminal boxes by peak cooling CFM, minimum heating flow, and reheat capacity

Ad placeholder (leaderboard)

A variable-air-volume terminal box throttles conditioned air to a single zone and, when fitted with a reheat coil, adds heat on cold mornings or in interior-perimeter zones. Sizing it well means matching the inlet to the peak cooling airflow while keeping the minimum flow high enough for ventilation and heating, but low enough to save fan and reheat energy.

How it works

The peak cooling CFM comes from the zone’s Manual J sensible load. The minimum airflow is set as a fraction of that peak for indoor air quality:

min CFM = peak CFM x (min % / 100)

The reheat coil delivers heat into the minimum airflow. From the sensible-heat equation, the airflow needed to carry the heat without overshooting the allowed supply temperature rise is:

Q = 1.08 x CFM x dT
CFM_for_heat = heating BTU/h / (1.08 x max rise)

The controlling minimum is the larger of the IAQ minimum and the heat-driven minimum. The coil capacity in kilowatts is BTU/h / 3412, and hot-water flow in GPM is BTU/h / (500 x coil dT).

Selection tips and notes

Pick the smallest standard inlet whose catalog maximum covers the peak CFM, so the box operates inside its pressure-independent range. Avoid grossly oversizing: a box running near a closed damper measures flow poorly and hunts. Always confirm the minimum setpoint against ASHRAE 62.1 ventilation rather than a rule of thumb, and verify the coil selection on the manufacturer’s performance data at your entering air and water temperatures.

Ad placeholder (rectangle)