Temperature Correction Derating Calculator (NEC 310.15)

Derate conductor ampacity for ambient temperatures above 30 °C using NEC correction factors

Ad placeholder (leaderboard)

Why ambient heat shrinks a conductor’s rating

A conductor’s ampacity is the current it can carry without its insulation exceeding its rated temperature. The published value in NEC Table 310.16 assumes the surrounding air is at 30°C. When the ambient is hotter — a rooftop conduit baking in the sun, a boiler room, a packed equipment closet — there is less of a temperature gap for the conductor to dissipate its own heat into, so the same current would drive the insulation past its limit. The code handles this with a multiplier from Table 310.15(B)(1) that you apply to the base ampacity.

How it works

The corrected ampacity is simply:

corrected = base_ampacity × temperature_factor

The factor depends on both the ambient temperature band and the insulation rating. At the 30°C basis the factor is 1.0. Below 30°C it rises above 1.0 (cold air actually lets a conductor carry slightly more). Above 30°C it falls: a 75°C conductor at 46°C uses a factor of 0.82, so a 30 A base ampacity becomes about 24.6 A. The higher the insulation rating, the slower the factor falls, because the insulation can absorb more heat before failing.

Example and notes

Take a 10 AWG copper THWN conductor with a 35 A base ampacity in the 75°C column. In a 50°C ambient the factor is 0.75, giving 26.25 A of usable ampacity — a 28% reduction that can easily push a circuit over the line if you sized it for the table value. Remember to combine this with the bundling adjustment when more than three current-carrying conductors share a raceway, and to use the highest ambient the run actually sees. For rooftop conduit, NEC 310.15(B)(3)(c) adds a temperature adder above the measured air temperature; add that adder before entering the ambient here.

Ad placeholder (rectangle)