Solar PV String Fuse Sizing Calculator (NEC 690.9)

Size string combiners and source-circuit fuses per NEC 690.9 for multi-string PV arrays.

Ad placeholder (leaderboard)

Get the string fuse wrong and you either nuisance-trip in full sun or fail to protect a faulted module from back-feed. This calculator applies the NEC 690.9 and 690.8 overcurrent rules: it takes module short-circuit current and the module’s maximum series fuse rating, then recommends a compliant string fuse and the minimum source-circuit conductor ampacity.

How it works

The chain of code multipliers produces the familiar 1.56 factor, then the result is rounded up to a standard fuse and checked against the module’s printed limit:

max circuit current = 1.25 × Isc            (690.8, irradiance margin)
min OCPD rating      = 1.25 × max current    (690.9, continuous duty)
                     = 1.25 × 1.25 × Isc = 1.56 × Isc
string fuse          = next standard ≥ 1.56 × Isc,  but ≤ module max series fuse
conductor ampacity   ≥ max(1.56 × Isc, fuse rating)  after derating

Standard fuse sizes used here are the common PV values: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60 A. If the required fuse would exceed the module maximum series fuse, the configuration itself must change.

Example and notes

A module with Isc of 9.5 A needs at least 1.56 × 9.5 = 14.8 A, so the next standard fuse is 15 A. If the module datasheet lists a maximum series fuse of 20 A, the 15 A fuse is fine and the source-circuit conductor must carry at least 14.8 A after temperature derating. Always confirm the number of parallel strings: with two strings, back-feed is limited and series fuses may not be required at all, but three or more parallel strings almost always need them.

Ad placeholder (rectangle)