Solar Battery Bank Calculator

Size a solar battery bank with the correct Ah formula — autonomy, DoD, efficiency, cell config.

Ad placeholder (leaderboard)
Enjoying the tools? Go Pro for £4.99 (one-time) and remove all ads — forever, on this device. Remove ads — £4.99

A solar battery bank calculator that applies the standard off-grid engineering formula to size a storage bank precisely — covering daily load, days of autonomy, chemistry depth of discharge, round-trip efficiency, temperature derating, and series-parallel cell configuration in a single interactive tool. Whether you are sizing a rooftop backup system, an off-grid cabin, a narrowboat or a motorhome, the calculation chain is the same, and the calculator walks through every step so you can see exactly why each number changes when you adjust an input.

How it works

The sizing engine is built around the canonical battery bank formula used throughout off-grid solar engineering:

Required nominal Ah = (Daily Wh × Autonomy days × Temperature factor) ÷ (System voltage × DoD × Round-trip efficiency)

Four things divide into the denominator, each one inflating the bank size you need:

  • System voltage converts energy (Wh) into capacity (Ah). A 24 V system needs half the Ah of an equivalent 12 V system for the same stored energy.
  • Depth of discharge (DoD) is the maximum safe draw fraction. Lead-acid batteries are limited to 50% DoD; LiFePO4 (LFP) safely reaches 80%. Because only the usable slice of the bank matters, the total nominal capacity must be scaled up by 1/DoD.
  • Round-trip efficiency captures heat losses during both charge and discharge. Flooded lead-acid is around 80%, AGM around 85%, LFP around 97%, and lithium-ion NMC around 95%. Every 1 Wh of load actually demands 1/efficiency Wh of stored capacity.
  • Temperature factor inflates the result to compensate for cold-weather capacity loss — a battery in a 0 °C shed delivers meaningfully less than its nameplate Ah.

The cell configuration step resolves the raw Ah figure into a real wiring layout. Cells in series add voltages; cells in parallel add capacities. The calculator computes series count as ⌈system voltage ÷ cell voltage⌉ (ceiling division, so voltage always meets the target), and parallel count as ⌈required Ah ÷ cell Ah⌉. The product of the two is the total cell count. The configured capacity will always equal or slightly exceed the requirement because whole cells are indivisible.

The solar charging section then asks a separate but equally important question: can your panel array replenish the bank each day, and how long does a full recharge take from empty? Panel charge current is panel watts × controller efficiency ÷ bus voltage; recharge hours are configured Ah × DoD ÷ that current; sun-days are recharge hours ÷ peak sun hours per day.

Worked example

A cabin uses a 200 W fridge for 24 hours, a 60 W LED lighting circuit for 5 hours, and a 30 W phone/laptop charger for 4 hours per day:

ApplianceWattsHoursWh/day
Fridge200244,800
Lighting605300
Chargers304120
Total5,220 Wh

With 3 days autonomy, a 24 V LFP bank (80% DoD, 97% efficiency, no temperature derating):

Required Ah = (5,220 × 3 × 1.0) ÷ (24 × 0.80 × 0.97) = 840 Ah nominal (≈ 20.2 kWh)

Using 100 Ah / 3.2 V LFP cells: 8 in series for 24 V, ⌈840 ÷ 100⌉ = 9 parallel strings — 72 cells total giving 900 Ah / 21.6 kWh configured.

ChemistryDoDEff.Required AhRequired kWh
LFP80%97%841 Ah20.2 kWh
Lead-acid50%80%1,631 Ah39.1 kWh
AGM50%85%1,535 Ah36.8 kWh

The table shows why LFP dominates modern off-grid installs despite higher upfront cost — the bank is roughly half the size of a lead-acid bank for identical usable energy. A 1,000 W panel array at 95% MPPT into a 24 V bus provides 39.6 A and recharges the LFP bank (900 Ah × 80% = 720 Ah to refill) in about 18.2 hours — roughly 5 sun-days at 3.8 h peak sun. Doubling the panel to 2 kW cuts that to 2.5 days.

Every figure recomputes instantly in your browser; nothing is uploaded or stored externally.

Ad placeholder (rectangle)