Motor Overload (OL) Heater Sizing Calculator

Size motor overload protection from FLA, service factor, and temperature rating per NEC 430.32.

Ad placeholder (leaderboard)

Running overload protection guards a motor against sustained overcurrent that would overheat its windings, and the NEC sizes it from the motor nameplate full-load amperes. This calculator applies the NEC 430.32 percentages, 125% or 115% depending on the motor’s service factor and temperature rise, and shows both the nominal trip current and the 430.32(C) maximum for single-phase and three-phase motors.

How it works

The overload trip is a percentage of the nameplate FLA, never the NEC table FLC:

service factor ≥ 1.15  OR  temp rise ≤ 40°C   →  nominal = FLA × 125%, max = FLA × 140%
all other motors                              →  nominal = FLA × 115%, max = FLA × 130%

You set the relay or heater so it trips at or just above the nominal value, and you may raise it toward the maximum only if nuisance tripping occurs during normal operation.

Example and tips

A 10 HP three-phase motor with a 28 A nameplate FLA and a 1.15 service factor gets 28 × 1.25 = 35 A nominal, with a ceiling of 28 × 1.40 = 39.2 A. A motor without that service factor would use 28 × 1.15 = 32.2 A nominal. Tips: always read the FLA off the motor nameplate rather than a table, since the two values differ; the overload protects the motor and is distinct from the much larger short-circuit branch protection; and only step up toward the maximum if the motor genuinely cannot start at the nominal setting.

Ad placeholder (rectangle)