Medium-Voltage Cable Sizing Calculator (5–35 kV)

Size MV feeder cables for shielded 5 kV–35 kV systems with ampacity and voltage-drop check.

Ad placeholder (leaderboard)

Sizing cable for primary distribution

Medium-voltage feeders — the 5 kV to 35 kV cables that move power between substations, switchgear, and large loads — must carry the load current without overheating and deliver acceptable voltage at the far end. Both checks depend on the conductor size and how the cable is installed. This calculator sizes a copper MV conductor for ampacity, then verifies voltage drop.

How it works

Sizing happens in two steps. First, ampacity: the tool selects the smallest standard copper size whose rated current for the chosen installation method — direct buried, in conduit, or in cable tray — meets or exceeds the load. These ampacities follow representative NEC Table 310.60 and IEEE Std 835 values for shielded MV cable.

Second, voltage drop. For a three-phase circuit:

Vdrop = sqrt(3) × I × L_kft × (R·cosθ + X·sinθ)

where R and X are the cable resistance and reactance per 1000 feet and the angle comes from the power factor. The drop is reported in volts and as a percent of the line-to-line voltage, checked against a 3% target. If the smallest ampacity-adequate conductor exceeds 3% drop, step up a size.

Example and notes

A 260 A load in conduit on a 15 kV system over 500 ft at 0.9 power factor selects a conductor sized for that ampacity and shows a voltage drop well under 3%. Always apply ambient, grouping, burial-depth, and soil thermal-resistivity corrections to the listed ampacities, and confirm short-circuit withstand, shield sizing, and grounding separately. This is a preliminary sizing aid, not a substitute for an engineered cable study.

Ad placeholder (rectangle)