kVA to Amps Converter

Convert kilovolt-amperes to amps for single-phase, split-phase, and three-phase systems

Ad placeholder (leaderboard)

Reading a transformer nameplate in amps

Transformers, generators, and UPS units are rated in kVA — apparent power — but electricians need amps to size conductors, breakers, and disconnects. The conversion depends only on the kVA and the voltage, never on power factor, because kVA already bundles the real and reactive components together. This converter handles single-phase and three-phase systems at all the common North American voltages and shows the exact formula it used so you can check the work.

How it works

For a single-phase (or split-phase line-to-line) system the line current is:

I = kVA × 1000 / V

For a balanced three-phase system the apparent power is √3 × V × I, so solving for current gives:

I = kVA × 1000 / (√3 × V)

with V always the line-to-line voltage and √3 ≈ 1.732. Because three-phase spreads the same apparent power across three conductors, the same kVA at the same voltage produces a noticeably lower per-line current than single-phase would.

Example and notes

A 75 kVA three-phase transformer at 480 V has a full-load current of 75 × 1000 ÷ (1.732 × 480) ≈ 90.2 A. The same 75 kVA single-phase at 240 V would draw 312.5 A — over three times the current — which is exactly why distribution is done three-phase at higher voltage. Use the result as the starting full-load current: for continuous loads multiply by 1.25 before selecting the overcurrent device, round up to the next standard breaker size, and verify the conductor ampacity (including any temperature or bundling derating) separately.

Ad placeholder (rectangle)