Oversized chilled-water pipe wastes copper or steel and money; undersized pipe is noisy and pumps hard. This calculator applies the continuity equation against ASHRAE velocity limits to pick the smallest Schedule 40 steel pipe that stays quiet, then reports the friction head you will pay for that choice.
How it works
Sizing is driven by velocity, and head loss is computed separately for the chosen size:
Q (cfs) = GPM × 0.002228
A (ft²) = Q / V_limit (continuity Q = V × A)
diameter = smallest standard ID whose actual V ≤ V_limit
head loss = f × (100/D) × V² / (2g) (Darcy-Weisbach, per 100 ft)
The friction factor f comes from the Swamee-Jain approximation using a steel
roughness of 0.00015 ft, and Reynolds number is based on chilled water near
50 °F. The tool also lists every standard size so you can see the velocity and
head trade-off across the range.
Example and notes
A 120 GPM main held to 4 ft/s lands on roughly 3-inch Schedule 40 pipe, running near 3.3 ft/s with about 2 ft of head loss per 100 ft. Bumping the velocity limit to 8 ft/s would allow 2-inch pipe but more than triples the friction head, so the pump and pipe trade against each other. Always add fitting and equipment losses on top of the straight-pipe figure before selecting a circulator.